ESUY copper ground wire
Structure and technical data
- Conductor material: Bare copper strands
- Conductor class: finely stranded, 7-wire
- Overall screen: braiding of bare copper wires
- Outer jacket material: special PVC mixture
- Sheath color: transparent
- Test Voltage: 2kV
- Insulation resistance: min 20 MOhm x km
- Ampacity: (only briefly) see VDE 0105 Part 1/5.75
burning value (1 sec.): > 300 A/mm² - smallest bending radius: fixed 10 x d
moves 12 x d - Operating temperature: fixed min/max -40 °C / +70 °C
Estimated min/max -5 °C / +70 °C - Brandverhalten: flammwidrig nach IEC 60332-1
- Standard in Anlehnung an VDE 0682/0683 und DIN 46338/46438 ESUY
application
as a safety grounding rope for grounding purposes where a very high degree of flexibility
required
is used, for example, for repairs to overhead power lines on railways,
for grounding
the current-carrying parts of the high-voltage systems of the utility companies as well as for
Earthing devices and equipotential bonding on machine parts and IT systems.
particularities
• Extra-fine bare copper bundle strands
• Very robust thanks to copper braiding over bundled strands
• LBS-free/silicone-free (at production)
• cold-resistant
cross-section | construction | Outer-Ø mm | Cu-Weight kg/km | total weight kg/km | Artivle number |
---|---|---|---|---|---|
16 | 4200 x 0,07 | 9 | 180 | 240 | T5000002 |
25 | 3234 x 0,10 | 10,7 | 280 | 340 | T5000003 |
35 | 4557 x 0,10 | 12,4 | 415 | 470 | T5000004 |
50 | 6370 x 0,10 | 14,6 | 585 | 680 | T5000005 |
70 | 8967 x 0,10 | 17,5 | 795 | 920 | T5000006 |
95 | 120005 x 0,10 | 20,8 | 1090 | 1240 | T5000007 |
120 | 15435 x 0,10 | 23,2 | 1360 | 1525 | T5000012 |
150 | 18865 x 0,10 | 26,2 | 1650 | 1950 | T5000013 |
185 | 25580 x 0,10 | 30,3 | 2150 | 2400 | T5000014 |
240 | 30600 0,10 | 33,0 | 2750 | 3100 | T5000016 |
- Weitere Anfertigungen auf Anfrage
- Alle Angaben ohne Gewähr
- Sollten Sie Fragen zu diesem Produkt haben, können Sie uns gerne telefonisch oder über unser Kontaktformular erreichen.
Datenblatt herunterladen