Letronic Bus-Combi L2/FIP 7-wire 1x2x0,64Ø+3x1.0
Application
Data cable with integrated power supply for the bus-logic of SIEMENS field-net Sinec L2 DP (acc. to DIN 19245 part 3 and EN 50170), for fieldbus system FIP (Factory Instrumentation Protocol) as well as for high performance data networks with 150 nominal impedance. The cable is designed for the system-defined transmission rates of 1.5 Mbit/s, 2.5 Mbit/s and 12 Mbit/s, the transmission characteristics conform to the system and guarantee a high operating security during data transmission.
The cable is intended for limited flexible use and for permanent installation in dry and damp interiors. The double screening ensures a reliable transmission of data It is suitable for installation in electromagnetically bonded areas.
Data pairs: stranded conductor: bare copper, 0.22 mm² (24AWG), 7 x 0.2
insulation: PE, core diameter approx. 2.5 mm
coding: cores red and green
stranding: 2 cores together with 2 fillers (core-filler-core-filler)
screening: plastic laminated aluminium-foil , metal-side outwards,
braid of tinned copper
Cores of power supply: stranded conductor: bare copper, 1.0 mm² (18AWG), 19 x 0.25
insulation: PE, core diameter approx. 1.7 mm;
core colour: green/yellow, black and blue.
Stranding: screened data pair with 3 cores twisted to power supply,
wrapping: one layer of non woven tape.
Sheath: PVC, violet RAL 4001, Outer diameter approx. 9.8 mm
Electrical characteristics at 20°C
Data transmissions pairs: Loop resistance max. Ohm/km 186
Screen resistance: max. Ohm/km 10
Insulation resistance: min. GOhmxkm 5
Mutual capacitance at 800 Hz nom. nF/km 28
Impedance at 9.6 kHz Ohm 270 ± 27
at 30.25 kHz Ohm 185 ± 18.5
at 3 to 20 kHz Ohm 150 ± 15
Line attenuation at 9.6 kHz max. dB/100 m 0.3
at 38.4 kHz max. dB/100 m 0.4
at 4 kHz max. dB/100 m 2.5
at 16 MHz max. dB/100 m 4,9
Transfer impedance at 20 MHz max. mOhm/m 10
Nominal velocity of propagation nom. 0,81c
Cores power supply Conductor resistance max.Ohm/km 26
Insulation resistance min. MOhmx km 20
Cable core:
Peak operation voltage Ueff V 100
(not for purposes of power/high voltage current)
Test voltage Ueff V 1500
Mechanical and thermal characteristics
Minimum bend radius static mm 60
flexible mm 90
Pulling force min.N 100
Temperature range static °C - 40 up to + 80
flexible °C - 5 up to + 50
Burning load kWh/m approx. 0,260
Flammability flame retardant to VDE 0482, part 265-2-1 / IEC 60 332-1
Article-Numer 4431126411
- Weitere Anfertigungen auf Anfrage
- Alle Angaben ohne Gewähr
- Sollten Sie Fragen zu diesem Produkt haben, können Sie uns gerne telefonisch oder über unser Kontaktformular erreichen.
Datenblatt herunterladen