UL/cUL 10203 AWG 24 (tp)

Construction

Core:

  • Conductor:                          tin plated copper (19x0,127mm)
  • Insulation material:                FEP
  • Diameter:                           (1,63 - 1,8)mm
  • average thickness of insulation:    max. 0,63mm

 

Technical Data

 

  • Test voltage(U rms):                10 kV AC (Sparktest)
  • Operating voltage(U rms):           1.000 V AC
  • Resistance at 20°C:                 max. 83,3 Ω/km
  • Temperature range:                  -100°C to 150°C
  • Bending radius fixed installation:  7,5 x diameter
                        free movement:  15  x diameter
  • weight:                             6,9 kg/km
  • printing:                           acc. UL 10203 E472542 

 

RoHS-compliant (2011/65/EU)
EC Low Voltage Directive 2014/35/EU

Articlenumer: 5768124010


  • Other formats available on request
  • All data and products subject to change
  • If you have any questions regarding this product, please feel free to call us or drop us a message via the contact form.