UL 3578 105°C 600V VW-1 (Copy)

Single core 6,0mm²                                            

  • Conductor:                                  84 x 0,30 mm  blank (copper strands)
  • Core insulation:                            XL-PE 4,9 +/- 0,2 mm 
  • Core color:                                 black sim. RAL 9005, semi-gloss
  • Printing:                                   acoording to UL
  • Cable weight:                               70 kg/km                         

Mechanical values:

  For fixed installation, limited flexible using

  • Bending radius:                  ≥ 7,5 x Cable diameter (fixed)
                                     ≥ 15 x Cable diameter (moved) 

Flame resistance:

  • UL 758/1581/2556 (Horizontal, VW-1)
  • DIN EN 60332-2-2 (20 sec.)

Flame resistance:

  • Fixed: - 40°C bis + 105°C
  • Moved: - 25°C bis + 105°C

Electrical vallues:

  • Nominal voltage:       600 V AC
  • Testing voltage:       6000 V AC (Sparktest online)
  • Conductor resistance:  max. 3,5 Ω /km (20°C)
  • Insulation resistance: min. 100 MΩ x km (20°C)

Additional:
Cable

  • halogenfree according to DIN VDE 0472 Teil 815 und DIN EN 60754-1
  • PWIS-, CFC-, PVC and siliconfree
  • oil resistant according to DIN EN 60811-404 (168h 100°C)
  • oil. and fuel resistant
  • Smoke density according to DIN EN 61034 (transmission/light transmittance >/= 60%)
  • Corrosivity of the fire gases according to IEC 60754-2 and DIN EN 50267-2-2 (measurement of pH value + electrical conductivity)
  • FRNC
  • UV-, oxygen-, ozone- and weather resistant (color may fade)
  • Generally good chemical resistance

 

Article number: UL35786010


* when used as intended 
** when bent carefully
 


  • Other formats available on request
  • All data and products subject to change
  • If you have any questions regarding this product, please feel free to call us or drop us a message via the contact form.