Letronic e.K. is official distributor of Lapp Cable.
NHXMH 3G1,5
Supplier-ID: 16020003
Description
For installation over, on, in or under the plaster, In brickwork and concrete, except direct embedding in vibrated or compressed concrete, In dry, damp and wet interiors, For buildings or industrial plants with a high density of people or valuable assets, Bare copper wire conductor, Core insulation: Polyethylene (PE), Filling compound over the core assembly, Outer sheath made of halogen-free polymer compound, Based on VDE 0250 part 214, Flame-retardant according to IEC 60332-1-2, No flame propagation according to IEC 60332-3-24, The use of halogen-free materials greatly reduces the formation of toxic dioxins and furans in the event of a fire, Prevents costly damages to buildings and equipment caused by the formation of toxic acid fumes in fires during combustion,
Specification | Value |
---|---|
Nominal cross section conductor | 1.5 |
Core insulation | Other |
Core identification | Colour |
Flame retardant | In accordance with EN 60332-3-24 |
Nominal voltage U | 500 |
Colour outer sheath | Grey |
Material outer sheath | Other |
Conductor category | Class 1 = solid |
Protective conductor | Yes |
Operating temperature, flexible | - - - |
Operating temperature, fix | -40 - 70 |
Nominal voltage U0 | 300 |
Screen | No |
Number of cores | 3 |
Halogen free (acc. EN 50267-2-2) | Yes |
Max. conductor temperature | - |
Outer diameter approx. | 8.5 |
Low smoke (acc. EN 61034-2) | Yes |
Diameter conductor | - |
Conductor material | Cu, bare |
Lead sheath | No |
Drain wire | No |
Insulation integrity | No |
Suspension element | None |
Armouring/reinforcement | None |
Protective barrier | None |